变换炉泄漏原因分析及检修措施 - 202003 - 肥料与健康
变换炉泄漏原因分析及检修措施
Cause Analysis and Maintenance Measures of Shift Converter Leakage
摘要:

变换装置第3变换炉出口焊缝多处出现泄漏,经宏观检查和实验室取样分析,确定其为氯化物应力腐蚀开裂所致。通过将新管件的焊缝堆焊材料升级为镍基合金,有效解决了泄漏问题,消除了影响装置安全运行的重大隐患。

关键词:
Abstract:

There are many leaks in the welding seam at the outlet of the third shift converter in the shift unit. After macro inspection and laboratory sampling analysis, it is determined that the leakage is caused by chloride stress corrosion cracking. By upgrading the weld surfacing material of the new pipe fittings to nickel-based alloys, the leakage problem is effectively solved, and major hidden dangers that affect the safe operation of the unit are eliminated.

Keyword: